Table C: Separation and Physical
Protection for Premises Inside Wiring
| Type of Wire Involved | Minimum Separation |
Wire Crossing Alternatives |
|
| Electric Supply | Bare light or power | 5ft. | No Alternative |
| Open wiring not over 300 volts | 2 in. | See Note I | |
| Wires in conduit, or in armored or nonmetallic sheath cable, or power ground wires | None | N/A | |
| Radio & Television | Antenna lead-in and ground wires | 4 in. | See Note I |
| Signal or Control Wires | Open wiring or wires in conduit or cable | None | N/A |
| Communication Wires | Community television systems coaxial cables with grounded sheilding | None | N/A |
| Telephone Drop Wire |
Using fused-protectors Using fuseless protector or where no protector wiring from transformer |
2 in. None |
See Note I N/A |
| Sign | Neon signs and associated wiring from transformer | 6 in. | No Alternatives |
| Lighting System | Lightning rods and wires | 6 ft. | See Wiring Separations |
| Note I: If minimum separations cannot be obtained, additional protection of a plastic tube, wire guard, or two layers of vinyl tape extending two inches beyond each side of object being crossed must be provided. | |||